Control, Measurement & Energy · Course

The Measurement Boundary and the Four Options

Lesson 5 of 10 23 min read
Found this useful?

A drive is fitted to a booster pump and the supplier promises a saving. Twelve months later the owner opens the electricity bills and finds no difference at all. The drive works exactly as promised: the saving is half a percent of what the site uses, and the site’s own bill moves by more than that from one month to the next for reasons nobody records. The mistake was made before the drive was bought, when nobody decided where the saving would be measured. This lesson shows how to draw the line round what a claim covers, what crosses that line, and how to choose a method of measurement that can see the saving. #MeasurementBoundary #EnergySavings #MeasurementAndVerification

Learning Objectives

By the end of this lesson, you will be able to:

  1. Draw a measurement boundary on a single-line sketch of a site and say which meter serves it
  2. Identify the interactive effects that cross a boundary and decide whether to estimate them or to move the boundary
  3. Describe the four options of the IPMVP in plain words
  4. Calculate a saving as a share of the metered energy and compare it with what that meter can show
  5. Choose a boundary and an option for a project and give the reason

Real-World System Problem: One utility meter and four projects



A small industrial site buys about 42,000 kWh of electricity a month through one utility meter. Behind that meter are a booster pump, a cold room, a store building with its lighting and cooling, and many other loads. The owner has four projects in hand: a variable speed drive on the pump, a power factor correction bank, a strip curtain and condenser cleaning for the cold room, and a lighting change in the store.

Each saving must be shown, and no instrument can read it: it is the difference between what was used and what would have been used without the project, which never happened.

The first decision is the same for all four projects: which part of the site does the claim cover, and which meter stands at the edge of that part? The utility meter is free to use and sees everything. A meter on one machine costs money and sees only that machine.

MColdroomDriveandpumpOtherloadsStore:lights,coolingutility supplyutility meter42,000 kWh a monthmain board
The site as a single-line sketch

Fundamental Theory: Where the claim begins and ends



The measurement boundary

The measurement boundary is a closed line drawn on the sketch of the site. Everything inside the line is covered by the claim. Every energy flow that crosses the line must be measured, or estimated with a stated reason. Everything outside the line is not part of the claim.

A boundary is a choice, not a fact of the site. Two choices are common. The first is a small boundary round the equipment that was changed. It needs its own meter.

PumpDriveotherloadsmain board. .........mpower..meter..........(F).water to the building.flow...........inside: pump and drive only
Boundary 1: round one pump and its drive

The second is a large boundary round the whole site. Its meter already exists.

MColdroomPumpOtherloadsStoreutility supply.........................utility meter.....................................
Boundary 2: round the whole site

The small boundary gives a clear signal, because the pump is the only thing inside it, but it costs a meter and knows nothing of what the project does to the rest of the site. The large boundary catches every effect of the project, and also every unrelated change on the site.

Whatever the boundary, write down its static factors: the features inside it that affect the energy and are expected not to change, such as set points, shifts, floor area and the list of equipment. If one changes later, the saving must be corrected, as non-routine adjustments shows.

Interactive effects

An interactive effect is a change in energy outside the measurement boundary that is caused by the project inside it. The standard example is lighting: almost all the electricity in a light fitting becomes heat in the room, so with lamps of lower power in a cooled building, the cooling plant outside the boundary has less heat to remove.

Room air..............boundary: lighting...heat.120 fittings...............heatelectricity(measured)Coolingplantelectricity(outside)(not measured)
Lighting heat crosses the boundary

There are three honest ways to treat an interactive effect.

  • Estimate it by an engineering calculation, with every assumption written down. Application 2 does this.
  • Move the boundary outward until the effect is inside it and is measured.
  • Leave it out, and say in the report that it was left out and why (usually because it is small against the saving).

The dishonest way is to count the effects that add to the saving and to stay silent about those that reduce it.

The four options

The International Performance Measurement and Verification Protocol (IPMVP), published by the Efficiency Valuation Organization, groups the ways of determining a saving into four options. The description here uses this course’s own words and goes only as far as the options are widely described in public. The current edition of the protocol decides what each option requires, and a contract that names the protocol means that edition, not this lesson.

OptionBoundaryWhat is measuredIn plain words
ARound the changed equipment (retrofit isolation)The key parameter. The rest is estimated and agreedMeasure the power, agree the hours
BRound the changed equipment (retrofit isolation)All parameters that decide the energyMeter the equipment itself
CThe whole facilityThe utility meter, with a baseline modelRead the site’s own meter and adjust for conditions
DWhole facility or part of itEnergy is found by a simulation calibrated to real dataModel the building when the data do not exist

In Option A the parameter that the project changes is measured, and one it does not change is estimated and agreed between the parties: a weakness both sides accept for a low cost of measurement. Agreed does not mean unchecked: write down where the estimate came from (a time switch setting, a log, a record), and support it with a short log of the on and off state where you can, because the saving moves with it in full proportion. In Option B nothing that matters is estimated. In Option C the weather and the working pattern differ between periods, so the comparison needs a baseline model: a formula, fitted to past data, for the energy the site uses under given conditions. Option D serves where there is no baseline to measure, such as a new building; none of the four projects needs it.

The signal against the meter

The size of a saving matters less than its size against the energy inside the boundary. A small saving at a large meter is like a whisper in a crowded hall; at a small meter it is a whisper in a quiet room. Let be the saving over a period and the energy that the boundary meter records over the same period. The share is

Metered energy is never perfectly steady: even after a good baseline model has removed the effect of weather and working days, each day differs from the model by a random amount. The coefficient of variation of the root mean square error, written CV(RMSE), is the typical size of that daily difference as a fraction of the mean daily energy. Over days the random differences partly cancel.

What a meter can show after m days

is the standard uncertainty of the baseline energy summed over days, as a fraction of that energy. is the expanded uncertainty, which covers about 95 percent of cases. A saving with smaller than cannot be told from zero.

A guide that is commonly quoted for whole-facility methods is that the expected saving should be a sizeable share of the metered energy, often quoted as more than about 10 percent. Treat this as a commonly quoted guide and check the protocol itself for what it says and under what conditions.

The data interval decides a great deal. Take a 3 percent saving on a site with only monthly bills, whose baseline model has a monthly scatter of 5 percent (an example value). After 12 bills, percent and percent. After a whole year the 3 percent saving is still at the edge of what the bills can show. With daily readings and a scatter of 4.74 percent a day, the same 3 percent equals after 10 days by the simple form.

The cost of measuring

Measurement is paid for from the saving. A meter, its installation by a licensed electrician, a logger and the time to check the data all have a cost. A small project with a certain result deserves a cheap method. A large project, or one whose result depends on how people use the equipment, deserves a careful one.

A second reason for the whole facility is a saving that exists only on the bill. A demand charge is calculated by the utility from its own meter, so that meter is the only place where the saving can be seen.

Application 1: A boundary and an option for each project



Step 1: Each saving against the utility meter

Click to reveal the shares
  1. Site energy in a year.

    This is 1,381 kWh on a mean day. ✅

  2. Project A.

    The drive saves about half a percent of the site’s energy, which is 221 kWh in a month. ✅

  3. Project C. The room saves kWh a day, which is 4,270 kWh a year.

    The cold room measures save less than one percent of the site’s energy. ✅

Step 2: What the utility meter can show

Click to reveal the comparison
  1. One month (30 days). The scatter of one day is 4.74 percent of 1,381 kWh, which is 65.5 kWh.

    In kWh this is kWh. The saving of project A in a month is 221 kWh, less than a third of what the meter can show. ✅

  2. One year (365 days).

    In kWh this is 2,501 kWh, against a saving of 2,650 kWh. After a whole year the saving is only just equal to the expanded uncertainty of the best case. ✅

  3. Days needed.

    Then the saving only equals its own uncertainty; to know project A within a tenth of itself would take 100 times as long. ✅

  4. Conclusion. The utility meter cannot prove project A. It cannot usefully prove project C either. Both need a smaller boundary. ✅

Step 3: Choose for each project

Click to reveal the four choices
  1. The choices.

    ProjectBoundaryOptionReason
    A, pump drivePump and driveB: retrofit isolation, all parameters measured0.53 percent of the site. The load varies, and power and flow can both be logged
    B, power factor bankWhole site at the utility meterC: whole facilityThe saving is in the demand and surcharge lines of the bill, which only the utility meter sets
    C, cold roomThe cold roomB: retrofit isolation, with a baseline model0.85 percent of the site. Energy depends on door minutes and temperature
    D, lightingThe lighting circuitsA: key parameter measuredPower is steady and easy to measure. Hours are agreed

    No two projects have the same answer for the same reason. ✅

  2. Project A. A power meter on the pump’s supply and a flow meter on its discharge record everything that decides the pump’s energy. The flow is logged because a year with more water pumped is a year with more energy, with or without the drive. ✅

  3. Project B. This project saves 172,880 currency units a month and almost no kWh. The quantities to follow are the monthly maximum demand in kVA and the surcharge, both taken from the bill. Record the site’s peak real power in kW with them, because a higher peak load raises the kVA for a reason that has nothing to do with the bank. ✅

  4. Project C. The room needs a sub-meter, a door-open timer and an outdoor temperature sensor, and a baseline model because the conditions of the two periods differ. If the room had its own utility meter, the choice would be the whole facility at that meter, with the same model. ✅

  5. Project D. The power of the fittings is the key parameter: it is what the project changes. The hours are not changed by the project, so they are agreed. The cooling plant is outside the boundary, and Application 2 calculates that interactive effect. ✅

Step 4: Check the signal inside the new boundaries

Click to reveal the check
  1. Project A inside its boundary.

    The same 0.883 kW is 0.53 percent at the utility meter and 37.7 percent at the pump’s meter. ✅

    Check the new meter before the baseline starts. Compare its kW with a portable power meter at the same moment (they should agree within a few percent). Confirm that the current transformer (CT) ratio set in the meter matches the CTs fitted, and that each CT faces the right way: a reversed CT makes its phase read low or negative. A meter error that stays the same in both periods scales the saving by the same factor; an error corrected between the periods creates a false saving or hides a real one.

  2. Project C inside its boundary. percent of the room’s energy. ✅

  3. Against the guide. Both shares are far above the commonly quoted 10 percent. A saving that is invisible at one boundary is plain at another, and the kWh have not changed. ✅

  4. Check with the script. The Python script prints 0.526 and 0.847 percent of the site, an expanded uncertainty of 717 kWh for a month and 2,501 kWh for a year, 325 and 125 days, and 37.7 and 44.8 percent inside the small boundaries. These agree with the hand values. ✅

Application 2: The interactive effect of the lighting change



Step 1: Lighting energy inside the boundary

Click to reveal the lighting saving
  1. Power removed. Each fitting falls from 72 W to 36 W.

    The lighting load falls by 4.32 kW. ✅

  2. Lighting energy saved.

    This is half of the 36,288 kWh a year the old fittings used. ✅

Step 2: Cooling energy outside the boundary

Click to reveal the interactive effect
  1. Cooling load removed. By the stated assumption, 80 percent of the lighting heat reached the cooling plant.

    The cooling plant has 14,515 kWh less heat to remove. ✅

  2. Cooling electricity saved. The plant uses 1 kWh of electricity for each 2.6 kWh of heat.

    This saving appears at the cooling plant’s supply, not on the lighting circuit. ✅

Step 3: Total, money and a check

Click to reveal the total
  1. Total.

    The interactive effect adds 30.8 percent to the lighting saving. ✅

  2. Money. Lighting: currency units a year. Cooling: . Total: 284,721 currency units a year. ✅

  3. Check a second way. The two steps combine into one factor.

    The factor and the step-by-step values agree, and the script prints the same numbers. ✅

  4. How much rests on the assumptions. With a COP of 2.0 the cooling saving is 7,258 kWh, and with a COP of 3.5 it is 4,147 kWh. The lighting figure of 18,144 kWh does not move. ✅

  5. A heated building. In a building that is heated, the sign is the opposite: the lamps were giving useful heat, the heating system must now supply it, and the interactive effect reduces the saving. ✅

Verify It in Python



The script calculates what the utility meter can show after a month and a year, the share of each saving at the two boundaries, and the interactive effect of the lighting change. It saves one plot: the smallest saving the site meter can show against the length of the period, with the two projects drawn as level lines.

boundary_signal_against_meter.py
"""Measurement boundary: can the saving be seen on the meter, and an interactive effect."""
import numpy as np
import matplotlib.pyplot as plt
PRICE = 12.00 # currency units per kWh
# ---------- Part 1: the signal against the meter ----------
SITE_MONTH = 42_000.0 # kWh a month on the utility meter
SITE_YEAR = 12 * SITE_MONTH
SITE_DAY = SITE_YEAR / 365.0
CV_DAILY = 0.0474 # CV(RMSE) of a daily whole-site baseline model
def expanded_percent(days, cv=CV_DAILY):
"""Expanded uncertainty (2u) of the summed baseline, percent of its energy."""
return 100.0 * 2.0 * cv / np.sqrt(days)
print("Whole-site meter")
print(f" site energy {SITE_YEAR:.0f} kWh a year, {SITE_DAY:.1f} kWh a day")
print(f" one day's baseline scatter: {CV_DAILY * SITE_DAY:.1f} kWh")
for days, name in ((30, "month"), (365, "year")):
u = CV_DAILY * SITE_DAY * np.sqrt(days)
print(f" one {name}: u = {u:.0f} kWh ({100 * CV_DAILY / np.sqrt(days):.3f} %), "
f"U = {2 * u:.0f} kWh ({expanded_percent(days):.2f} %)")
projects = { # saving in kWh a year
"A pump drive": 2650.0,
"C cold room": (26.1 - 14.4) * 365.0,
}
for name, kwh in projects.items():
share = kwh / SITE_YEAR
days = (2.0 * CV_DAILY / share) ** 2
print(f" {name}: {kwh:.0f} kWh a year = {100 * share:.3f} % of the site, "
f"{kwh / 12:.0f} kWh a month, days to equal U: {days:.0f}")
for pct in (3.0, 10.0):
print(f" a {pct:.0f} % saving equals U after {(2 * CV_DAILY / (pct / 100)) ** 2:.1f} days")
CV_MONTHLY = 0.05 # example scatter of a model built on monthly bills
u12 = CV_MONTHLY / np.sqrt(12)
print(f" monthly bills, CV(RMSE) 5 %: after 12 bills u = {100 * u12:.2f} %, "
f"U = {200 * u12:.2f} %")
print("Inside the retrofit isolation boundary of project A")
print(f" saving {0.883:.3f} kW of {2.345:.3f} kW = {100 * 0.883 / 2.345:.1f} %")
print(f" cold room: {26.1 - 14.4:.1f} of 26.1 kWh a day = {100 * (26.1 - 14.4) / 26.1:.1f} %")
# ---------- Part 2: project D, lighting with a cooling interaction ----------
N, P_OLD, P_NEW, HOURS = 120, 72.0, 36.0, 4200.0
SHARE, COP = 0.80, 2.6 # stated assumptions
before = N * P_OLD * HOURS / 1000.0
after = N * P_NEW * HOURS / 1000.0
lighting = before - after
cooling_load = SHARE * lighting
cooling_elec = cooling_load / COP
total = lighting + cooling_elec
print("Project D: lighting change in a cooled store")
print(f" lighting energy before {before:.0f} kWh, after {after:.0f} kWh a year")
print(f" lighting energy saved {lighting:.0f} kWh a year")
print(f" cooling load removed {cooling_load:.0f} kWh of heat a year")
print(f" cooling electricity saved {cooling_elec:.0f} kWh a year")
print(f" total {total:.0f} kWh a year, factor {total / lighting:.3f}")
print(f" money: lighting {lighting * PRICE:.0f}, cooling {cooling_elec * PRICE:.0f}, "
f"total {total * PRICE:.0f} currency units a year")
print(f" second way: {lighting:.0f} x (1 + {SHARE} / {COP}) = "
f"{lighting * (1 + SHARE / COP):.0f} kWh")
for cop in (2.0, 3.5):
print(f" COP {cop}: cooling {SHARE * lighting / cop:.0f}, "
f"total {lighting * (1 + SHARE / cop):.0f} kWh")
# ---------- Plot ----------
days = np.arange(7, 731)
fig, ax = plt.subplots(figsize=(8, 5))
ax.loglog(days, expanded_percent(days), label="smallest saving the site meter can show")
for name, kwh in projects.items():
ax.axhline(100 * kwh / SITE_YEAR, linestyle="--", linewidth=0.9)
ax.text(8, 100 * kwh / SITE_YEAR * 1.07, name + " as a share of the site")
ax.axhline(10.0, color="gray", linewidth=0.8)
ax.text(8, 10.7, "10 percent guide")
ax.set_xlabel("days in the reporting period")
ax.set_ylabel("percent of the metered energy")
ax.set_title("What a whole-site meter can and cannot show")
ax.legend()
fig.tight_layout()
fig.savefig("boundary_signal_against_meter.png", dpi=120)
print("Saved boundary_signal_against_meter.png")

Expected output

Whole-site meter
site energy 504000 kWh a year, 1380.8 kWh a day
one day's baseline scatter: 65.5 kWh
one month: u = 358 kWh (0.865 %), U = 717 kWh (1.73 %)
one year: u = 1250 kWh (0.248 %), U = 2501 kWh (0.50 %)
A pump drive: 2650 kWh a year = 0.526 % of the site, 221 kWh a month, days to equal U: 325
C cold room: 4270 kWh a year = 0.847 % of the site, 356 kWh a month, days to equal U: 125
a 3 % saving equals U after 10.0 days
a 10 % saving equals U after 0.9 days
monthly bills, CV(RMSE) 5 %: after 12 bills u = 1.44 %, U = 2.89 %
Inside the retrofit isolation boundary of project A
saving 0.883 kW of 2.345 kW = 37.7 %
cold room: 11.7 of 26.1 kWh a day = 44.8 %
Project D: lighting change in a cooled store
lighting energy before 36288 kWh, after 18144 kWh a year
lighting energy saved 18144 kWh a year
cooling load removed 14515 kWh of heat a year
cooling electricity saved 5583 kWh a year
total 23727 kWh a year, factor 1.308
money: lighting 217728, cooling 66993, total 284721 currency units a year
second way: 18144 x (1 + 0.8 / 2.6) = 23727 kWh
COP 2.0: cooling 7258, total 25402 kWh
COP 3.5: cooling 4147, total 22291 kWh
Saved boundary_signal_against_meter.png

In the plot, the falling line is the smallest saving the site meter can show. It meets the line of project C after about four months and the line of project A only near the end of a year.

Common Mistakes



  • Looking for a small saving on the utility meter. Calculate the share first. A saving of half a percent of the metered energy is hidden by the ordinary scatter of the site.
  • Fitting the meter after the project. The baseline must be measured at the same boundary before anything changes, and it cannot be recovered afterwards.
  • Counting an interactive effect that adds to the saving and ignoring one that reduces it. List both, with the assumption behind each.
  • Reporting measured and estimated values as one number. In Option A the estimated parameter is a weakness that both sides accepted, and the report must show it.
  • Treating a cost saving as an energy saving. The power factor bank lowers the bill and saves almost no kWh.

Summary



  • The measurement boundary is the closed line round what the claim covers. Every energy flow that crosses it is measured or estimated with a stated reason.
  • An interactive effect is a change outside the boundary caused by the project inside it. It is estimated, brought inside by moving the boundary, or left out with a statement.
  • The IPMVP groups methods into four options: key parameter measured (A), all parameters measured (B), whole facility with a baseline model (C) and calibrated simulation (D). The current edition of the protocol decides the detail.
  • A saving must be compared with the energy inside its boundary. Project A is 0.53 percent of the site meter and 37.7 percent of the pump’s own meter.
  • By the simple form, a meter shows a saving only when its share exceeds . More readings help. A smaller boundary helps much more.
  • The lighting change saves 18,144 kWh a year measured, and about 5,583 kWh more in cooling under two stated assumptions.

Exercises



1. A site uses 60,000 kWh a month. A project is expected to save 9,000 kWh a year. The daily baseline model of the site has a CV(RMSE) of 6 percent. Find the saving as a share of the metered energy, the expanded uncertainty after 60 days by the simple form, and the days after which the saving equals the expanded uncertainty.

Answer

The site uses kWh a year, so the share is percent. percent, which is larger than 1.25 percent, so the saving cannot be seen after 60 days. days, and that is only the point where the saving equals its own uncertainty.

2. A motor that runs at a steady load is replaced. Its power is measured as 9.8 kW before and 9.1 kW after. The parties agree 5,000 operating hours a year. Find the saving by Option A. Then find the saving if the true hours are 4,200, and say which number the contract pays on.

Answer

kWh a year. With 4,200 hours the real saving is kWh. The contract pays on the agreed 3,500 kWh, because the hours were estimated and agreed. This is the risk of Option A, and the reason the agreed value must have a source.

3. In a building with no cooling, 200 fittings of 58 W are replaced by fittings of 30 W. They operate 3,000 hours a year. The building is heated by electric resistance heaters for 1,200 of those hours, and in those hours 75 percent of the lighting heat was useful heating. Find the lighting saving and the net saving in kWh a year.

Answer

Lighting: kWh. In the heated hours the lamps release kWh less heat, and the heaters must replace kWh, at 1 kWh of electricity for each kWh of heat. Net saving: kWh a year. The interactive effect has the opposite sign and removes 30 percent of the lighting saving.

4. A site uses 90,000 kWh a month. Leaks in its compressed air system are repaired, and the saving is expected to be 20,000 kWh a year at the one compressor, whose load changes with production. Choose a boundary and an option, and give the reason with a number.

Answer

The share at the utility meter is percent, far below the commonly quoted guide of about 10 percent for whole-facility methods. Draw the boundary round the compressor and meter its energy all year (retrofit isolation, all parameters measured), with production or air demand logged as the independent variable. Agreed hours would not be honest here, because the load is not steady.

References



  • Efficiency Valuation Organization, International Performance Measurement and Verification Protocol (IPMVP): Core Concepts, current edition.
  • ASHRAE, Guideline 14-2014: Measurement of Energy, Demand, and Water Savings, ASHRAE, 2014.
  • B. L. Capehart, W. C. Turner and W. J. Kennedy, Guide to Energy Management, 8th edition, Fairmont Press, 2016.
  • ISO 50015:2014, Energy management systems: Measurement and verification of energy performance of organizations: General principles and guidance.


© 2021-2026 SiliconWit®. All rights reserved.
utility supply M utility meter 42,000 kWh a month main board Drive and pump Cold room Store: lights, cooling Other loads One meter at the top sees every load at once.
The site as a single-line sketch
boundary: lighting 120 fittings electricity measured heat Room air heat Cooling plant outside electricity not measured Less heat from the new lamps means less work for the cooling plant, outside the boundary.
Lighting heat crosses the boundary
Predict first

A drive saves 2,650 kWh a year on a site that uses 504,000 kWh a year through one utility meter. After a full year, can the saving be seen on that meter?

utility meterpump's meter saving: 0.53 percent 37.7 percent the same 0.883 kW in both bars
measurement boundary lighting: 18,144 kWh a year, measured power heat cooling plant about 5,583 kWh a year, estimated
See it: when does the saving rise above the scatter?

Saving as a share of the meter, f
Smallest share the meter shows, day
Days until f equals U

The simple form, the best case: the daily differences are independent and the model is exact. The curve is U = 2 × CV(RMSE) / √m, the expanded uncertainty of the energy summed over m days, as a share of that energy. The level line is the saving's share of the energy at the boundary. Both scales are logarithmic. The pump's meter uses the site's 4.74 percent scatter only as an example: the lesson gives no scatter for it.

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. A project is expected to save 2 percent of a site's energy. The site's daily baseline model has a CV(RMSE) of 5 percent. By the simple form, after how many days does the saving equal the expanded uncertainty of the site meter?

2. The same lighting change is made in a building that has no cooling but is heated by electric heaters in the cold months. The boundary is round the lighting circuits. What does the interactive effect do?

3. A pump whose flow follows production gets a new impeller. The saving is about 1 percent of the site's energy. Which boundary and option fit?

Watch it build: where the claim begins and ends
M 42,000 kWh a month Pump Cold room Store Other Inside the line: the claim.Every flow across it: measured. Pump meter: 7,035 kWh a yearThe saving is 37.7 % of it Site meter: the same savingis only 0.53 %, 221 kWh a month Coolingheat Lights: 18,144 kWh14,515 heat ÷ 2.6 = 5,583 kWh Total 23,727 kWhThe 5,583 is estimated: say so.
  1. One utility meter, 42,000 kWh a month, and four groups of load behind it.
  2. A small boundary round the pump: its own meter sees the saving as 37.7 % of 7,035 kWh.
  3. The whole site as the boundary: the same 2,650 kWh is only 0.53 % of the meter.
  4. New lamps save 18,144 kWh inside; their missing heat saves 5,583 kWh at the cooling plant outside.
  5. Estimate it, move the boundary, or leave it out and say so. Here the total is 23,727 kWh.