Pumps in Parallel and in Series

Lesson 8 of 10 23 min read
Found this useful?

A site is short of water at the busiest hour, so the owner buys a second pump, identical to the first, and connects it beside the first. The owner expects twice the flow. The flow meter shows 15 percent more, and the electricity meter shows 27 percent more. Nothing is wrong with either pump. Two pumps share one pipe system, and the pipe system decides what the second pump can add. This lesson shows how to combine pump curves in parallel and in series, how to find what each pump does, and how to decide when the second pump should run. #ParallelPumps #SeriesPumps #PumpStations

Learning Objectives

By the end of this lesson, you will be able to:

  1. Build the combined curve of identical pumps in parallel and in series
  2. Solve the duty point of the combined pumps on a system curve and find each pump’s flow, efficiency and electrical input
  3. Explain why two pumps in parallel give less than twice the flow, and when they come close to it
  4. Predict when the weaker of two unequal pumps is pushed back to shut-off
  5. Decide from the electrical input at which flow a second pump should start

Real-World System Problem: A booster station with two pumps



The booster pump of this course supplies buildings whose demand moves between 6 and 24 m³/h. One pump at full speed reaches 23.34 m³/h on the distribution system, so it cannot meet the top of the demand. The station is therefore built with two identical pumps, side by side, drawing from the same tank and feeding the same main.

Two questions follow. What do the two pumps deliver together? And over which part of the demand should the second pump run? Start it too early and the station pays for two pumps working far from their best efficiency point; too late and it cannot hold the pressure.

Two pumps can also be connected one after the other, the second taking the discharge of the first. That serves a different kind of system, and the wrong arrangement gives almost nothing for the cost of a pump.

Pump 2Pump 1Pump 2Pump 1Parallel: same head, flows addQ1+Q2Series: same flow, heads addH1+H2
Two pumps in parallel and two pumps in series

Fundamental Theory: Combining pump curves



Pumps in parallel

Two pumps in parallel draw from the same suction header and discharge into the same main. The pressure is the same at both inlets and the same at both outlets, so both pumps work at the same head. The main carries the sum of their flows.

To draw the combined curve, take one head, read the flow of each pump at that head, and add the flows. Repeat for other heads.

For identical pumps the rule becomes simple. At any head, each pump carries the same flow, so each carries the total flow divided by the number of pumps. If one pump has the curve , then identical pumps in parallel have the curve below.

Identical pumps in parallel

is the total flow in the main and is the number of pumps running. The shut-off head does not change. The curve is stretched to the right by the factor .

For two boosters, , with in m³/h.

A common mistake is to add the heads of pumps in parallel. Two pumps of 42 m shut-off head, side by side, still give 42 m at shut-off. They give more flow, not more head.

Why the flow does not double

The combined curve is twice as wide, but the duty point is where it crosses the system curve, which rises with flow: more flow in the same pipes needs more friction head. To supply it, each pump moves left on its own curve and delivers less than it did alone. Two taps filling one bucket through one thin hose do not fill it twice as fast.

Hsteep system●B_two pumps●A●Cflatsystem_one pumpQone pumpsteep: smallflat: nearlyalonegaindouble
The second pump on a steep and on a flat system

On a steep system curve, the duty point moves from A to B: a little more flow at a clearly higher head. On a flat system curve, where nearly all the head is static, it moves from A to C: almost twice the flow at almost the same head.

For identical pumps on a system curve , the duty flow has a closed form:

is the static head and is the friction coefficient of the system. The ratio depends only on , the steepness of the system curve compared with the steepness of the pump curve. With no friction () the ratio is 2. With very large friction it approaches 1. Twice the flow is a limit that a real system never reaches.

What happens to each pump

When the second pump starts, each pump moves back on its curve, toward shut-off. When one of two stops, the other moves out to the right, toward run-out, and carries far more than its share.

Check both movements. A pump moved back may work at low efficiency, with recirculation. A pump left alone works at its largest flow, where its shaft power and NPSH required are highest. Size the motor and check the suction for one pump running alone, not for its share when both run.

Pumps in series

Two pumps in series carry the same water, one after the other, so the flow is the same in both. Each adds its head. To draw the combined curve, take one flow, read the head of each pump at that flow, and add the heads.

Identical pumps in series

The shut-off head is multiplied by . The largest flow does not change.

For two boosters, .

Series pumps suit a system that needs more head than one pump can give: a high static lift, or a long, narrow pipe with a steep curve. The multistage borehole pump of this course is the same idea in one casing, with several impellers on one shaft, each adding its head to the same flow.

Choosing the arrangement

Unequal pumps

Parallel pumps do not need to be identical, but the weaker pump is at risk. Take the booster, , beside a smaller pump with . Both must work at the same head. Whenever that head is 36 m or more, the smaller pump delivers nothing: held at shut-off by the pressure of the larger pump, it turns all of its power into heat in its casing. At 36 m the larger pump alone carries 22.36 m³/h. On the distribution system of this course the two settle at 35.96 m, the larger pump carrying 22.43 m³/h and the smaller only 1.35 m³/h, so a small rise in system resistance pushes the smaller pump to nothing. The same happens to one of two identical pumps that is worn or runs slower. Each pump in parallel needs its own non-return valve, so that a pump at shut-off or at rest is not driven backwards.

H42large pump36●●_ small__ pump_Q22.4Above 36 m the small pump delivers nothing.
Unequal pumps: the small pump is pushed back

Speed control with more than one pump

When each pump has its own drive, identical pumps that run together are given the same speed, so that they share the flow equally. The affinity laws then apply to each pump with its own share of the flow. The efficiency of each pump is found from its equivalent full-speed flow, which is its share divided by the speed ratio .

Application 1: Two boosters in parallel at full speed



Step 1: The combined curve and the duty point

Click to reveal where two pumps settle
  1. Combined curve. At equal head each pump carries half of the total flow.

    The combined curve has the same shut-off head and one quarter of the coefficient. ✅

  2. Duty point. Set the combined curve equal to the system curve.

    The two pumps together deliver 26.87 m³/h. ✅

  3. Head.

    The system curve gives the same: m. The duty point is 26.87 m³/h at 39.83 m. ✅

Step 2: What each pump does

Click to reveal each pump’s share
  1. Flow of each pump.

    Each pump carries 13.44 m³/h, against 23.34 m³/h when it runs alone. On its own curve, m, which agrees. ✅

  2. Efficiency of each pump.

    Each pump works at 65.5 percent, at 75 percent of its best efficiency flow. ✅

  3. Power of each pump. With :

    Each pump takes 2.525 kW, so the station takes 5.05 kW. ✅

  4. Energy for each cubic metre.

    One pump alone uses kWh/m³. With two pumps each cubic metre costs 11 percent more. ✅

Step 3: The gain and its cause

Click to reveal why the flow did not double
  1. Gain in flow.

    The second pump adds 15.1 percent to the flow, and 27 percent to the electrical input (5.05 kW against 3.96 kW). ✅

  2. Where the head went. The friction head of the system is . With one pump it is 13.46 m. With two pumps it is 17.83 m. The 15 percent of extra flow needs 4.37 m of extra head, and the pumps can give it only by moving back on their curves to 13.44 m³/h each. ✅

  3. What doubling would need. Twice the flow is 46.68 m³/h. At that flow the system needs m. Two pumps in parallel never give more than 42 m. Doubling is impossible on these pipes. ✅

  4. Check with the closed form. Here and .

    The ratio is the same as in step 1. The system curve is twice as steep as the pump curve (), and that fixes the result. ✅

Step 4: A flat system and a steep system

Click to reveal the two opposite cases
  1. Flat system, one pump.

    One pump delivers 22.09 m³/h at 36.15 m. ✅

  2. Flat system, two pumps in parallel.

    Two pumps deliver 42.64 m³/h at 36.55 m, a gain of 93.1 percent. Each pump carries 21.32 m³/h, almost what it carried alone. ✅

  3. Steep system, one pump.

    One pump delivers 9.53 m³/h at 40.91 m. It works at 53 percent of its best efficiency flow, with an efficiency of 0.594. ✅

  4. Steep system, two pumps in parallel.

    The second pump adds 0.35 m³/h, which is 3.6 percent. It is almost useless here. ✅

  5. Steep system, two pumps in series. The combined curve is .

    The head is m, which is 37.5 m from each pump. The flow has doubled, and each pump now works at 19.36 m³/h with an efficiency of 0.678, close to its best. Each takes 3.31 kW. ✅

Application 2: When to start the second pump



Step 1: One pump at 18 m³/h

Click to reveal the single pump at the design flow
  1. Head the system needs.

    The hydraulic power is W, whichever pumps supply it. ✅

  2. Speed ratio. The pump curve at speed ratio must pass through 18 m³/h at 30.00 m.

    One pump runs at 89.8 percent of full speed. ✅

  3. Efficiency.

    The pump works close to its best efficiency point. ✅

  4. Electrical input.

    One pump takes 2.549 kW. ✅

Step 2: Two pumps at 18 m³/h

Click to reveal the two pumps sharing the same flow
  1. Speed ratio. Each pump carries 9 m³/h at the same 30.00 m.

    Both pumps run at 85.9 percent of full speed. ✅

  2. Efficiency.

    Each pump is far to the left of its best efficiency point. ✅

  3. Total electrical input. The hydraulic power is the same 1,469 W.

    Two pumps take 2.811 kW, which is 10 percent more than one pump for the same water. ✅

Step 3: The three flows and the crossing

Click to reveal the comparison and the flow where it changes
  1. The same steps at 22 and 24 m³/h.

    (m³/h)System head (m)One pump: (kW)Two pumps: (kW)
    1830.000.8980.6752.5490.8590.6122.811
    2233.950.9730.6543.6360.9180.6363.739
    2436.231.013not possiblenot possible0.9510.6454.293

    One pump takes less power at 18 and at 22 m³/h. ✅

  2. One pump cannot reach 24 m³/h. It would need a speed ratio of 1.013, above full speed. At full speed it gives 35.09 m at 24 m³/h, and the system needs 36.23 m. Its limit is the full-speed duty point, 23.34 m³/h. Two pumps deliver 24 m³/h at 95.1 percent of full speed and take 4.293 kW. ✅

  3. Where the two inputs are equal. The hydraulic power, the motor and the drive are the same for both arrangements, so the inputs are equal where the pump efficiencies are equal. A root finder gives

    Above 23.63 m³/h two pumps would take less power than one. ✅

  4. Compare with the limit of one pump. At 23.63 m³/h one pump would need , which it does not have. The crossing lies just beyond the 23.34 m³/h that one pump can reach. At 23.34 m³/h one pump takes 4.084 kW and two take 4.104 kW. So over the whole range that one pump can serve, one pump takes less power. ✅

  5. Check a second way. The efficiency formula is symmetric about 18 m³/h. The two arrangements have equal efficiency when one pump is as far above 18 as each of two pumps is below it. At 23.63 m³/h, one pump has , which is 5.49 above. Each of two pumps has , which is 5.49 below. Both give . ✅

61823.342426.87m³/hone pump, speedtwo pumps,control: less powerequal speedat every flow hereone pump is at full speed:start the second pump
Which pumps run across the range of demand

Verify It in Python



The script solves the duty points of one and two pumps on the three system curves, the pair of unequal pumps, and the speed-control comparison of Application 2. It finds the flow of equal power with a root finder and saves one plot.

parallel_series.py
"""Two booster pumps in parallel and in series, and when to start the second."""
import numpy as np
from scipy.optimize import brentq
import matplotlib.pyplot as plt
RHO, G = 998.0, 9.81
ETA_MOTOR, ETA_DRIVE = 0.88, 0.97
def pump(q, r=1.0): # one booster at speed ratio r
return 42.0 * r**2 - 0.012 * q**2
def eta(q_full): # efficiency at the full-speed flow
return 0.68 - 0.0012 * (q_full - 18.0) ** 2
def system(q): # the site's distribution system
return 22.0 + 0.0247 * q**2
def p_in(q, head, eta_pump, drive=1.0):
"""Electrical input in kW for flow q (m3/h) at the given head."""
return RHO * G * (q / 3600.0) * head / 1000.0 / eta_pump / (ETA_MOTOR * drive)
def duty(n_parallel, sys_curve, n_series=1):
"""Duty point of identical pumps at full speed on a system curve."""
return brentq(lambda q: n_series * pump(q / n_parallel) - sys_curve(q), 0.1, 80.0)
# ---------- Application 1: full speed, no drive ----------
print("Application 1: parallel pumps on H = 22 + 0.0247 Q^2, full speed")
q1, q2 = duty(1, system), duty(2, system)
for n, q in ((1, q1), (2, q2)):
each = q / n
print(f" {n} pump(s): Q = {q:.2f} m3/h, H = {system(q):.2f} m, each {each:.2f} m3/h, "
f"efficiency {eta(each):.4f}, input each {p_in(each, system(q), eta(each)):.3f} kW, "
f"total {n * p_in(each, system(q), eta(each)):.3f} kW, "
f"{n * p_in(each, system(q), eta(each)) / q:.4f} kWh/m3")
print(f" gain in flow from the second pump: {100 * (q2 / q1 - 1):.1f} %")
print(f" friction head: {system(q1) - 22:.2f} m with one pump, {system(q2) - 22:.2f} m with two")
def flat(q):
return 36.0 + 0.0003 * q**2
f1, f2 = duty(1, flat), duty(2, flat)
print(f" flat system 36 + 0.0003 Q^2: one pump {f1:.2f} m3/h at {flat(f1):.2f} m, "
f"two pumps {f2:.2f} m3/h at {flat(f2):.2f} m, gain {100 * (f2 / f1 - 1):.1f} %")
# ---------- Series ----------
def steep(q):
return 30.0 + 0.12 * q**2
s1, s2, sp = duty(1, steep), duty(1, steep, n_series=2), duty(2, steep)
print("Series pumps on H = 30 + 0.12 Q^2")
print(f" one pump: {s1:.2f} m3/h at {steep(s1):.2f} m, efficiency {eta(s1):.4f}")
print(f" two in series: {s2:.2f} m3/h at {steep(s2):.2f} m "
f"({steep(s2) / 2:.2f} m each), efficiency {eta(s2):.4f}, "
f"input each {p_in(s2, steep(s2) / 2, eta(s2)):.3f} kW")
print(f" two in parallel on the same system: {sp:.2f} m3/h at {steep(sp):.2f} m")
# ---------- Unequal pumps in parallel ----------
def q_big(h):
return np.sqrt(max(42.0 - h, 0.0) / 0.012)
def q_small(h): # small pump: H = 36 - 0.02 Q^2
return np.sqrt(max(36.0 - h, 0.0) / 0.02)
h_u = brentq(lambda h: q_big(h) + q_small(h) - np.sqrt((h - 22.0) / 0.0247), 22.5, 41.9)
print("Unequal pumps in parallel on the site's system")
print(f" small pump delivers nothing at 36 m or more; there the large pump gives "
f"{q_big(36.0):.2f} m3/h")
print(f" duty: H = {h_u:.2f} m, large pump {q_big(h_u):.2f}, small pump {q_small(h_u):.2f}, "
f"total {q_big(h_u) + q_small(h_u):.2f} m3/h")
# ---------- Application 2: speed control, one pump against two ----------
def speed_case(q_total, n):
"""Speed ratio, pump efficiency and total electrical input for n pumps."""
each, head = q_total / n, system(q_total)
r = np.sqrt((head + 0.012 * each**2) / 42.0)
e = eta(each / r)
return r, each / r, e, n * p_in(each, head, e, ETA_DRIVE)
print("Application 2: speed control on H = 22 + 0.0247 Q^2")
for q in (18.0, 22.0, 24.0):
print(f" Q = {q:.0f} m3/h, system needs {system(q):.2f} m")
for n in (1, 2):
r, q_eq, e, p = speed_case(q, n)
note = " NOT POSSIBLE, above full speed" if r > 1.0 else ""
print(f" {n} pump(s): r = {r:.4f}, Q_eq = {q_eq:.2f} m3/h, "
f"efficiency {e:.4f}, input {p:.3f} kW, {p / q:.4f} kWh/m3{note}")
q_x = brentq(lambda q: speed_case(q, 1)[3] - speed_case(q, 2)[3], 15.0, 26.0)
print(f" equal power at Q = {q_x:.2f} m3/h, where one pump would need "
f"r = {speed_case(q_x, 1)[0]:.4f}")
print(f" one pump at full speed reaches {q1:.2f} m3/h; there one pump takes "
f"{speed_case(q1, 1)[3]:.3f} kW and two take {speed_case(q1, 2)[3]:.3f} kW")
r_min = np.sqrt(22.0 / 42.0)
print(f" no flow below r = {r_min:.4f}")
# ---------- Plot ----------
qq = np.linspace(0.0, 50.0, 300)
fig, ax = plt.subplots(1, 2, figsize=(10.5, 4.5))
ax[0].plot(qq, pump(qq), label="one pump")
ax[0].plot(qq, pump(qq / 2.0), label="two in parallel")
ax[0].plot(qq, system(qq), "k", label="site system")
ax[0].plot(qq, flat(qq), "k--", label="flat system")
ax[0].plot([q1, q2], [system(q1), system(q2)], "o", color="black")
ax[0].plot([f1, f2], [flat(f1), flat(f2)], "s", color="black")
ax[0].set_ylim(20.0, 45.0)
ax[0].set_xlabel("flow (m3/h)")
ax[0].set_ylabel("head (m)")
ax[0].legend(fontsize=8)
qs = np.linspace(15.0, 25.5, 200)
one = np.array([speed_case(q, 1)[3] if speed_case(q, 1)[0] <= 1.0 else np.nan for q in qs])
two = np.array([speed_case(q, 2)[3] for q in qs])
ax[1].plot(qs, one, label="one pump, speed control")
ax[1].plot(qs, two, label="two pumps sharing equally")
ax[1].axvline(q1, color="gray", ls=":", label="limit of one pump")
ax[1].set_xlabel("flow (m3/h)")
ax[1].set_ylabel("electrical input (kW)")
ax[1].legend(fontsize=8)
fig.tight_layout()
fig.savefig("parallel_series.png", dpi=120)
print("Saved parallel_series.png")

Expected output

Application 1: parallel pumps on H = 22 + 0.0247 Q^2, full speed
1 pump(s): Q = 23.34 m3/h, H = 35.46 m, each 23.34 m3/h, efficiency 0.6457, input each 3.962 kW, total 3.962 kW, 0.1697 kWh/m3
2 pump(s): Q = 26.87 m3/h, H = 39.83 m, each 13.44 m3/h, efficiency 0.6550, input each 2.525 kW, total 5.050 kW, 0.1879 kWh/m3
gain in flow from the second pump: 15.1 %
friction head: 13.46 m with one pump, 17.83 m with two
flat system 36 + 0.0003 Q^2: one pump 22.09 m3/h at 36.15 m, two pumps 42.64 m3/h at 36.55 m, gain 93.1 %
Series pumps on H = 30 + 0.12 Q^2
one pump: 9.53 m3/h at 40.91 m, efficiency 0.5940
two in series: 19.36 m3/h at 75.00 m (37.50 m each), efficiency 0.6778, input each 3.311 kW
two in parallel on the same system: 9.88 m3/h at 41.71 m
Unequal pumps in parallel on the site's system
small pump delivers nothing at 36 m or more; there the large pump gives 22.36 m3/h
duty: H = 35.96 m, large pump 22.43, small pump 1.35, total 23.78 m3/h
Application 2: speed control on H = 22 + 0.0247 Q^2
Q = 18 m3/h, system needs 30.00 m
1 pump(s): r = 0.8983, Q_eq = 20.04 m3/h, efficiency 0.6750, input 2.549 kW, 0.1416 kWh/m3
2 pump(s): r = 0.8588, Q_eq = 10.48 m3/h, efficiency 0.6121, input 2.811 kW, 0.1562 kWh/m3
Q = 22 m3/h, system needs 33.95 m
1 pump(s): r = 0.9730, Q_eq = 22.61 m3/h, efficiency 0.6545, input 3.636 kW, 0.1653 kWh/m3
2 pump(s): r = 0.9182, Q_eq = 11.98 m3/h, efficiency 0.6365, input 3.739 kW, 0.1700 kWh/m3
Q = 24 m3/h, system needs 36.23 m
1 pump(s): r = 1.0135, Q_eq = 23.68 m3/h, efficiency 0.6413, input 4.320 kW, 0.1800 kWh/m3 NOT POSSIBLE, above full speed
2 pump(s): r = 0.9506, Q_eq = 12.62 m3/h, efficiency 0.6453, input 4.293 kW, 0.1789 kWh/m3
equal power at Q = 23.63 m3/h, where one pump would need r = 1.0058
one pump at full speed reaches 23.34 m3/h; there one pump takes 4.084 kW and two take 4.104 kW
no flow below r = 0.7237
Saved parallel_series.png

The row marked NOT POSSIBLE shows what one pump would take at 24 m³/h if it could run above full speed. In the right plot, the line for one pump stops at 23.34 m³/h and lies below the line for two pumps all the way to that limit.

Common Mistakes



  • Expecting twice the flow from two pumps in parallel. The gain depends on how steep the system curve is, and it is always less than double.
  • Adding heads for pumps in parallel, or adding flows for pumps in series. Parallel adds flows at equal head. Series adds heads at equal flow.
  • Sizing the motor and checking the NPSH for the shared flow. One pump running alone carries the largest flow, and that is the case to check.
  • Putting a weaker pump in parallel with a stronger one without checking the common head. Above its shut-off head the weaker pump delivers nothing.
  • Starting the second pump early “to share the load”. At the same total flow, two pumps far from their best efficiency point can take more power than one pump near it.

Summary



  • Identical pumps in parallel work at the same head and share the flow: . Identical pumps in series carry the same flow and add their heads: .
  • Two boosters in parallel on the distribution system deliver 26.87 m³/h at 39.83 m, each carrying 13.44 m³/h at 65.5 percent efficiency and taking 2.525 kW.
  • That is 15.1 percent more flow than one pump for 27 percent more power, because the extra flow needs 4.37 m more friction head.
  • On a flat system the same pair gives 93 percent more flow. On a steep system a parallel pump adds 4 percent, and a series pump doubles the flow.
  • A weaker pump in parallel delivers nothing when the common head reaches its shut-off head, here 36 m.
  • With speed control on this system, one pump takes less power than two at every flow it can reach. The inputs are equal at 23.63 m³/h, just beyond the 23.34 m³/h limit of one pump, so the second pump is started for capacity.

Exercises



1. One pump has the curve and the system has the curve ( in m³/h). Find the duty flow with one pump and with two identical pumps in parallel, and the gain in percent.

Answer

One pump: m³/h. Two pumps: the combined curve is , so m³/h at 41.18 m. The gain is 37.2 percent.

2. A system has the curve . Show that one booster () delivers nothing. Then find the duty point of two boosters in series, the head and efficiency of each, and the electrical input of each with a motor efficiency of 0.88 and no drive.

Answer

The static head, 50 m, is above the shut-off head of 42 m, so one pump delivers nothing. In series: , so m³/h at 72.97 m, which is 36.49 m each. . Each pump: kW, kW.

3. The booster () runs in parallel with a smaller pump (). Find the flow of each pump when the common head is 34 m, and when it is 38 m.

Answer

At 34 m: large pump m³/h, small pump m³/h, total 35.82 m³/h. At 38 m: large pump m³/h. The small pump cannot reach 38 m, so it delivers nothing and runs at shut-off.

4. For Application 2, find the speed ratio, the pump efficiency and the total electrical input at 20 m³/h with one pump and with two pumps.

Answer

The system needs m, and kW. One pump: , , , kW. Two pumps: , , , kW. One pump takes 6 percent less.

5. The two boosters have no drives. They run at full speed and a valve holds the total flow at 24 m³/h. Find the pump head, the head the valve takes, and the total electrical input (motor 0.88). Compare with the 4.293 kW of two pumps under speed control.

Answer

Each pump carries 12 m³/h at m. The system needs 36.23 m, so the valve takes 4.04 m. . Each pump: kW, kW. The total is 4.69 kW, which is 0.40 kW (9 percent) more than with speed control.

References



  • I. J. Karassik, J. P. Messina, P. Cooper and C. C. Heald, Pump Handbook, 4th edition, McGraw-Hill, 2008.
  • J. F. Gülich, Centrifugal Pumps, 3rd edition, Springer, 2014.
  • F. M. White, Fluid Mechanics, 8th edition, McGraw-Hill, 2016.
  • Y. A. Çengel and J. M. Cimbala, Fluid Mechanics: Fundamentals and Applications, 4th edition, McGraw-Hill, 2018.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

One booster pump delivers 23.34 m³/h into a distribution system. Of the 35.5 m of head at that flow, 22 m is static and the rest is friction. A second, identical pump is started in parallel with the first. How much more water does the station deliver?

See it: more pumps on the same pipes

Total flow
Head at the duty point
Each pump: flow
Each pump: efficiency
Total electrical input
Energy for each m³
Gain in flow over one pump
One pump alone

The black curve is one booster pump, H = 42 − 0.012 Q². The coloured curve is the combined curve of the pumps that run. In parallel the flows add at equal head, so the curve is stretched to the right. In series the heads add at equal flow, so it is stretched upward. The dashed curve is the system, 22 + k Q², with the static part fixed at the lesson's 22 m. The slider changes only the friction coefficient k, from a nearly flat system on the left to a steep one on the right. The gold dot is the duty point of the station. The red dot shows what each pump does on its own curve. The open circle is one pump alone on the same system. The pumps run at full speed with no drive, and the motor efficiency is 0.88. The maker's sheet for this pump ends at 28 m³/h, so no efficiency is shown for a pump beyond that flow.

+93 %+15 %+4 % flat systemthis sitesteep system one pumptwo pumps
large pumpsmall pumpheader 35.96 m 22.4 m³/h 1.4 m³/h it can make at most 36 m

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. Two boosters run in parallel on the distribution system and deliver 26.87 m³/h at 39.83 m. What does each pump do?

2. Two boosters run in parallel and the discharge valve of the station is closed for a moment. Each pump alone has a shut-off head of 42 m. What head does a gauge on the common discharge show?

3. On the lesson's system two pumps in parallel give 26.87 m³/h. The owner wants more and proposes a third identical pump in parallel. What does it add?

Watch it build: two boosters in parallel
Q 42 one pump two 22.444.7 36 42 m, not 84 A B 26.9 m³/h, +15 % each pump 13.4 m³/h
  1. One booster, H = 42 − 0.012 Q². Two side by side share one head and one main.
  2. At one head, add the flows: at 36 m, 22.4 m³/h becomes 44.7 m³/h.
  3. The shut-off head stays 42 m. Two pumps in parallel give more flow, not more head.
  4. On the system curve the flow rises only from 23.3 to 26.9 m³/h, 15 %. Each pump gives 13.4.
Parallel: same head, flows add Pump 1 Q1 Pump 2 Q2 Q1 + Q2 suction same head H at both pumps Series: same flow, heads add Pump 1 Pump 2 Q Q, head H1 Q, head H1 + H2
Two pumps in parallel and two pumps in series
0 10 20 30 40 20 25 30 35 40 45 Q, m³/h (total flow) H, m A B C +15 % +93 % two pumps in parallel, 42 − 0.003 Q² one pump 42 − 0.012 Q² steep system: this site 22 + 0.0247 Q² flat system, 36 + 0.0003 Q² A one pump alone: 23.34 m³/h at 35.46 m on this site; 22.09 m³/h at 36.15 m on the flat system B two pumps, steep system: 26.87 m³/h at 39.83 m, a small gain at a clearly higher head C two pumps, flat system: 42.64 m³/h at 36.55 m, nearly double at almost the same head
The second pump on a steep and on a flat system
0 5 10 15 20 25 30 30 32 34 36 38 40 42 44 Q, m³/h (total flow) H, m 42 m: large pump shut-off 36 m: small pump shut-off above 36 m the small pump delivers nothing C B A small pump share at B: 1.35 m³/h small pump, 36 − 0.02 Q² large pump 42 − 0.012 Q² both system, 22 + 0.0247 Q² A large pump alone on the system: 23.34 m³/h at 35.46 m B both pumps: 23.78 m³/h at 35.96 m; large 22.43, small only 1.35 C at 36 m the small pump stops delivering; the large pump alone gives 22.36 m³/h
Unequal pumps: the small pump is pushed back
6 18 24 26.87 23.34 m³/h one pump, speed control: less power at every flow here two pumps, equal speed best efficiency flow one pump is at full speed: start the second pump
Which pumps run across the range of demand