Tariffs, Maximum Demand and the Load Profile

Lesson 10 of 10 25 min read
Found this useful?

A site manager switches lights off for a month, and the bill falls by less than one percent. In the same month, two machines were restarted together after lunch on one day, and that single half-hour added more to the bill than the lights saved. The bill gives three or four numbers for a whole month, so it cannot show when the energy was used or which half-hour set the demand charge. A load profile, a list of the power in each half-hour, shows both. This lesson rebuilds a bill from its tariff and then reads one day of a profile to find where the money goes. #Tariffs #MaximumDemand #LoadProfile

Learning Objectives

By the end of this lesson, you will be able to:

  1. Rebuild a bill from its tariff: the energy charge, the demand charge and the power factor surcharge
  2. Calculate the load factor and the average demand of a site and explain what they mean for the price of each kWh
  3. Read a half-hourly load profile to find the base load, the peak and its cause
  4. Estimate the standing waste at night and its monthly cost
  5. Calculate the demand saving when loads that start together are staggered

Real-World System Problem: The monthly bill of a cold store



Site E is a cold store on a 200 kVA transformer. In one month its meter records 42,000 kWh, a maximum demand of 150 kVA and an average power factor of 0.78. The bill for that month is 773,760 currency units.

To reduce that total, the owner needs to know which machines produce which line. The energy line follows the kWh of every hour of the month, including the hours when nobody is on site. The demand line follows one half-hour only: the highest of about 1,440 in the month. The surcharge follows the average power factor.

The bill cannot separate them further. It does not say how much of the 42,000 kWh was used at night, or what was running in the half-hour of the peak. That needs a record of the power through the day.

Surcharge, a % ofthe two linesDemand chargekVA × priceEnergy chargekWh × priceAverage power factor(kWh and kvarh)Highest half-hourof the month, in kVAkWh of the month(every hour counts)
What each line of the bill is calculated from

Fundamental Theory: Energy, demand and time



The supply in this course is three-phase, 50 Hz, 415 V between lines (400 V is the IEC nominal and many countries use it). is real power in kW, is apparent power in kVA, and the power factor is .

The parts of a bill

Tariffs for industrial and commercial sites differ from one supplier to another, and they change. Most are built from the same few parts.

  • Energy charge. A price for each kWh. Some tariffs have one price. Others have different prices by time of day (time-of-use tariffs), with a lower price at night.
  • Demand charge. A price for each kVA, or each kW, of the maximum demand of the month. It pays for the capacity of lines and transformers that the supplier must keep ready for the site.
  • Power factor surcharge. A penalty when the average power factor is below a limit, or a charge for kvarh.
  • Fixed charges, levies and taxes. These are set by the supplier and the regulator, and the site cannot change them. Read them with care: in some countries, Kenya among them, several are charged for each kWh (a fuel cost charge, adjustments for exchange rate and inflation, levies), and a tax is added on top. A kWh saved then saves the base price and every one of those charges, so the true value of a kWh is often well above the printed energy price.

This course uses one example tariff. Energy costs 12.00 currency units per kWh. Demand costs 800 currency units per kVA of the month’s maximum demand. When the average power factor is below 0.90, a surcharge of 2 percent of the energy and demand charges is added for each 0.01 below 0.90. It is an example only. The structure is what matters, and your own tariff sheet gives the real rules.

How maximum demand is measured

The meter does not record the highest instant of current. It divides time into demand intervals, 30 minutes in this course, and calculates the average kVA of each interval. The maximum demand register keeps the highest average since it was last reset, usually once a month.

This averaging decides what can and cannot set the peak. The compressor motor of site E takes 186.9 kVA during a direct-on-line start and 28.8 kVA when it runs. If the start lasts 10 seconds (an example), it adds to the half-hour average only

kVA187start, about 10 saverage of the interval: 29.7 kVA29running at 28.8 kVA0030 min
A 10-second start inside a 30-minute demand interval

The starting current itself is therefore not what sets the maximum demand. What sets it is several machines that run together, each near full load, for most of one interval. This happens when a whole site is switched on at the start of a shift, after a break or after a power cut. In the first half-hour after a start, a refrigeration plant cools warm product and a conveyor clears the material that waited, so each machine is at its heaviest in the same interval.

Load factor

The load factor compares the energy that a site used with the energy it would have used at its maximum demand for every hour.

Load factor and average demand

is the energy in kWh, is the number of hours in the period, is the maximum demand in kW and is the average demand in kW. The load factor LF has no unit and lies between 0 and 1.

Use kW for both powers. If the meter gives the maximum demand in kVA, multiply by the power factor at the peak first.

A low load factor means a tall, narrow profile: a high peak that is used for few hours. The demand charge is then shared by few kWh, and each kWh is expensive.

A load factor can be raised in two ways, and only one of them is a saving. Lowering the peak for the same energy reduces the bill. Using more energy under the same peak raises the load factor and also raises the bill.

Base load, night load and standing waste

The base load is the power that a site takes when it is least active, the level that the profile never goes below. It is small in kW, but it runs for all 720 hours of a 30-day month. Each kW of base load is 720 kWh a month.

Part of the base load is necessary. A cold store must keep its evaporator fans, its controls and its security lighting. The other part is standing waste: equipment that is on when nobody needs it. Common examples are an air compressor that keeps a leaking pipe network under pressure, lights and air conditioning in empty rooms, and machines left in standby. Nights and rest days show this most clearly, because production is stopped.

Reading a profile

Staggering means that loads which now start together start one after another, so that their heaviest half-hours do not coincide. It lowers the demand charge and does not change the kWh. Shifting means moving a load to another time of day. It saves energy cost only on a time-of-use tariff, and it lowers the demand charge when the load leaves the peak half-hour.

Both have limits. The work must still be done and the product must stay cold. A profile shows what is possible, and the people who run the process decide what is acceptable.

Application 1: The bill of site E, line by line



Step 1: Energy and demand charges

Click to reveal the first two lines
  1. Energy charge.

    ✅

  2. Demand charge.

    One half-hour of the month produced this line. ✅

  3. Sum of the two. currency units. ✅

Step 2: Surcharge and total

Click to reveal the surcharge
  1. Rate. The power factor is below the limit, which is 12 steps of 0.01. The rate is percent. ✅

  2. Surcharge.

    ✅

  3. Total.

    The three lines are 65.1, 15.5 and 19.4 percent of the bill. ✅

Step 3: Average demand and load factor

Click to reveal the load factor
  1. Hours in the month. . ✅

  2. Average demand.

    ✅

  3. Maximum demand in kW.

    ✅

  4. Load factor.

    On average the site uses half of the peak that it pays for. ✅

Step 4: The price of each kWh, and a check

Click to reveal the average price
  1. Average price.

    The printed energy price is 12.00. The demand charge adds 2.86 and the surcharge adds 3.57. ✅

  2. Check a second way. Build the price from the load factor. The demand charge for each kWh is .

    The two routes agree. ✅

  3. Check with the script. The script prints the same three lines, the total of 773,760, a load factor of 0.499 and 18.42 per kWh. With the same maximum demand, a load factor of 0.30 would give 20.77 per kWh and a load factor of 0.70 would give 17.40. ✅

Application 2: One working day, half-hour by half-hour



kW120peak at 14:0010080604020004812162024
The day of the table: one mark for each half-hour

Each mark is placed at the nearest 20 kW. The low row is the base load, the row above it is the base load with the compressor, and the upper rows are the working day.

Step 1: The base load

Click to reveal the base load
  1. Lowest value. The lowest value in the table is 20.0 kW, and it occurs 12 times: 10 times at night and twice in the evening. The base load is 20.0 kW. ✅

  2. Check with the compressor. The other night values are all 44.2 kW, and , which is the compressor. Night is the base load with the compressor cycling on top of it. ✅

  3. Energy of the base load. a day. ✅

Step 2: Energy and load factor of the day

Click to reveal the energy
  1. Energy. Each value is an average over half an hour, so each one contributes its kW multiplied by 0.5 h. The sum of the 48 values is 2810.9.

    The base load is 34 percent of this. ✅

  2. Average demand. . ✅

  3. Load factor of the day.

    ✅

  4. Check against the bill. Thirty such days give about 42,160 kWh, within 0.4 percent of the 42,000 kWh on the bill, and the load factor agrees with the 0.499 of the month. The day is a fair picture of the month. ✅

Step 3: The peak and its cause

Click to reveal the peak
  1. Highest value. 117.0 kW in the interval that starts at 14:00. At a power factor of 0.78 this is , the maximum demand on the bill. ✅

  2. Next highest values. 106.7 kW at 12:30, 105.9 kW at 12:00 and 105.8 kW at 16:30. The ordinary working level is about 105 kW, and the peak stands 10 kW above it. ✅

  3. Cause. The peak follows the lunch break (35.1 kW at 13:00) and the next interval is only 82.2 kW. The staff report that the motors and the blast freezer restart together at 14:00. In that half-hour every load is at its heaviest at once. The morning does not show the same peak, because the loads are switched on in turn between 06:30 and 09:00. ✅

Step 4: Night energy and standing waste

Click to reveal the night waste
  1. Night energy. The 16 intervals from 22:00 to 06:00 contain ten values of 20.0 kW and six of 44.2 kW.

    ✅

  2. Split. The base load gives and the compressor gives 72.6 kWh. The compressor keeps the store cold, so its energy is needed. ✅

  3. Standing waste. Of the 20.0 kW base load, 9.0 kW is needed at night.

    This is 38 percent of the night energy. ✅

  4. Cost in a month.

    The waste at night is 6.3 percent of the kWh of the month. ✅

Step 5: Stagger the restart after lunch

Click to reveal the demand saving
  1. The 14:00 interval without the freezer.

    ✅

  2. The 14:30 interval with the freezer in its first half-hour. The table value of 82.2 kW contains the freezer at 20.0 kW. Replace it by 24.8 kW.

    Neither interval is now close to the working level of 105 kW. ✅

  3. New peak. The highest value of the day is now 106.7 kW at 12:30.

    The maximum demand falls by 13.2 kVA. ✅

  4. Demand charge.

    The demand charge falls from 120,000 to 109,440. The freezer runs half an hour later and uses the same kWh. ✅

  5. Check with the script. The script builds the day again with the freezer restart at 14:30. It prints 92.2 kW and 87.0 kW for the two intervals, a new peak of 106.7 kW at 12:30, the same 1405.4 kWh, and a demand charge that is lower by 10,560. ✅

Verify It in Python



The script builds the bill from the tariff rule. It then generates the day of Application 2 from its loads, with a fixed seed so that the table is the same on every run, reads the 48 values, and repeats the day with the staggered restart. The plot shows both days.

load_profile_and_bill.py
"""Site E: the bill from tariff G, and a 24-hour half-hourly load profile."""
import numpy as np
import matplotlib.pyplot as plt
RATE_KWH, RATE_KVA = 12.00, 800.0 # tariff G, currency units
PF_LIMIT, SURCHARGE_STEP = 0.90, 0.02 # 2 % for each 0.01 below 0.90
PF = 0.78 # site power factor, also at the peak
DAYS = 30
HOURS = 24.0 * DAYS
def bill(kwh, md_kva, pf_avg):
energy = kwh * RATE_KWH
demand = md_kva * RATE_KVA
points = max(0, int(round((PF_LIMIT - pf_avg) * 100.0)))
surcharge = SURCHARGE_STEP * points * (energy + demand)
return energy, demand, surcharge, energy + demand + surcharge
# ---------- Part 1: the bill and the load factor ----------
KWH, MD_KVA = 42000.0, 150.0
e, d, s, total = bill(KWH, MD_KVA, PF)
md_kw = MD_KVA * PF
print("Bill of site E (currency units)")
print(f" energy {e:,.0f} + demand {d:,.0f} = {e + d:,.0f}")
print(f" surcharge {s:,.0f}, total {total:,.0f}")
print(f" average price {total / KWH:.2f} per kWh "
f"({(e + d) / KWH:.2f} before the surcharge)")
print(f" maximum demand {md_kw:.0f} kW, average demand {KWH / HOURS:.2f} kW, "
f"load factor {KWH / (md_kw * HOURS):.3f}")
for lf in (0.30, KWH / (md_kw * HOURS), 0.70):
kwh = lf * md_kw * HOURS
print(f" same demand at load factor {lf:.3f}: {kwh:,.0f} kWh, "
f"{bill(kwh, MD_KVA, PF)[3] / kwh:.2f} per kWh")
# ---------- Part 2: build the day (48 half-hours, start times 00:00 to 23:30) ----------
SEED = 2026 # fixed, so the table is the same every run
t = np.arange(48) * 0.5 # start of each half-hour, in hours
BASE = 20.0 # kW, never switches off
COMP = 24.2 # compressor motor A when it runs
LIGHT, MOTORS = 18.0, 30.0 # full inputs of the working-hours loads
FREEZER_FULL, FREEZER_RUN = 24.8, 20.0 # first half-hour after a start, then steady
def between(a, b):
return (t >= a) & (t < b)
# compressor: 14 hours a day in whole half-hours (1 = running)
comp_on = np.zeros(48)
comp_on[between(22, 24) | between(0, 6)] = [1, 0, 0] * 5 + [1] # night: 6 of 16
comp_on[between(6, 22)] = ([1, 1, 0] * 11)[:32] # day: 22 of 32
light_on = between(6.5, 18)
motors_on = between(7, 13) | between(14, 17.5)
def day_profile(freezer_restart):
"""Half-hourly kW. freezer_restart is the afternoon start time in hours."""
r = np.random.default_rng(SEED)
light = LIGHT * r.uniform(0.80, 1.00, 48) * light_on # not all in use
motors = MOTORS * r.uniform(0.70, 0.90, 48) * motors_on # part load
motors[(t == 7) | (t == 14)] = MOTORS # first half-hour after a start
light[t == 14] = LIGHT # everything switched on after the break
fr_on = between(8.5, 13) | between(freezer_restart, freezer_restart + 3.5)
freezer = FREEZER_RUN * fr_on
freezer[(t == 8.5) | (t == freezer_restart)] = FREEZER_FULL
return np.round(BASE + COMP * comp_on + light + motors + freezer, 1)
kw = day_profile(14.0)
labels = [f"{int(h):02d}:{int(round(60 * (h % 1))):02d}" for h in t]
print("Half-hourly profile, kW (start of interval)")
for i in range(24):
print(f" {labels[i]} {kw[i]:6.1f} {labels[i + 24]} {kw[i + 24]:6.1f}")
# ---------- Part 3: read the day ----------
energy = kw.sum() * 0.5
peak = kw.max()
print("Reading the day")
print(f" base load (lowest value) {kw.min():.1f} kW, "
f"{kw.min() * 24.0:.0f} kWh a day, {100 * kw.min() * 24.0 / energy:.1f} % of the day")
print(f" energy {energy:.1f} kWh, average {energy / 24.0:.2f} kW")
print(f" peak {peak:.1f} kW at {labels[int(kw.argmax())]}, "
f"load factor {energy / (peak * 24.0):.2f}")
print(f" 30 such days: {DAYS * energy:,.0f} kWh")
order = np.argsort(kw)[::-1][:4]
print(" four highest half-hours: " +
", ".join(f"{labels[i]} {kw[i]:.1f}" for i in order))
night = between(22, 24) | between(0, 6)
e_night = kw[night].sum() * 0.5
ESSENTIAL = 9.0 # kW of the base load that must stay on
waste_kw = kw.min() - ESSENTIAL
waste_month = waste_kw * 8.0 * DAYS
print(f" night 22:00 to 06:00: {e_night:.1f} kWh, of which base "
f"{kw.min() * 8.0:.1f} and compressor {e_night - kw.min() * 8.0:.1f}")
print(f" standing waste {waste_kw:.1f} kW = {waste_kw * 8.0:.1f} kWh a night "
f"({100 * waste_kw * 8.0 / e_night:.0f} % of the night energy)")
print(f" = {waste_month:,.0f} kWh a month = {waste_month * RATE_KWH:,.0f} currency units")
# ---------- Part 4: stagger the afternoon restart ----------
kw2 = day_profile(14.5)
peak2 = kw2.max()
print("Freezer restarted at 14:30 and not at 14:00")
print(f" 14:00 {kw[28]:.1f} -> {kw2[28]:.1f} kW, 14:30 {kw[29]:.1f} -> {kw2[29]:.1f} kW")
print(f" new peak {peak2:.1f} kW at {labels[int(kw2.argmax())]}, "
f"energy {kw2.sum() * 0.5:.1f} kWh")
kva1, kva2 = round(peak / PF, 1), round(peak2 / PF, 1)
print(f" demand {kva1:.1f} -> {kva2:.1f} kVA, fall {kva1 - kva2:.1f} kVA")
print(f" demand charge {kva1 * RATE_KVA:,.0f} -> {kva2 * RATE_KVA:,.0f}, "
f"difference {(kva1 - kva2) * RATE_KVA:,.0f} a month")
b1 = bill(KWH, kva1, PF)[3]
b2 = bill(KWH, kva2, PF)[3]
print(f" whole bill with the surcharge: {b1:,.0f} -> {b2:,.0f}, "
f"difference {b1 - b2:,.0f}")
# ---------- Plot ----------
fig, ax = plt.subplots(figsize=(10, 4.5))
ax.step(t, kw, where="post", label="as measured")
ax.step(t, kw2, where="post", linestyle="--", label="freezer restart at 14:30")
ax.axhline(kw.min(), color="gray", linewidth=0.8)
ax.text(0.2, kw.min() + 2.0, f"base load {kw.min():.0f} kW")
ax.axhline(energy / 24.0, color="gray", linestyle=":", linewidth=0.8)
ax.text(0.2, energy / 24.0 + 2.0, f"average {energy / 24.0:.1f} kW")
ax.set_xlim(0, 24)
ax.set_xticks(range(0, 25, 2))
ax.set_xlabel("hour of the day")
ax.set_ylabel("half-hourly demand (kW)")
ax.set_title("Site E: one working day")
ax.legend()
fig.tight_layout()
fig.savefig("load_profile_and_bill.png", dpi=120)
print("Saved load_profile_and_bill.png")

Expected output

Bill of site E (currency units)
energy 504,000 + demand 120,000 = 624,000
surcharge 149,760, total 773,760
average price 18.42 per kWh (14.86 before the surcharge)
maximum demand 117 kW, average demand 58.33 kW, load factor 0.499
same demand at load factor 0.300: 25,272 kWh, 20.77 per kWh
same demand at load factor 0.499: 42,000 kWh, 18.42 per kWh
same demand at load factor 0.700: 58,968 kWh, 17.40 per kWh
Half-hourly profile, kW (start of interval)
00:00 44.2 12:00 105.9
00:30 20.0 12:30 106.7
01:00 20.0 13:00 35.1
01:30 44.2 13:30 60.7
02:00 20.0 14:00 117.0
02:30 20.0 14:30 82.2
03:00 44.2 15:00 100.5
03:30 20.0 15:30 104.5
04:00 20.0 16:00 80.0
04:30 44.2 16:30 105.8
05:00 20.0 17:00 103.8
05:30 20.0 17:30 37.8
06:00 44.2 18:00 44.2
06:30 61.3 18:30 44.2
07:00 66.3 19:00 20.0
07:30 83.1 19:30 44.2
08:00 86.6 20:00 44.2
08:30 87.4 20:30 20.0
09:00 101.0 21:00 44.2
09:30 102.6 21:30 44.2
10:00 81.7 22:00 44.2
10:30 103.0 22:30 20.0
11:00 105.4 23:00 20.0
11:30 77.9 23:30 44.2
Reading the day
base load (lowest value) 20.0 kW, 480 kWh a day, 34.2 % of the day
energy 1405.4 kWh, average 58.56 kW
peak 117.0 kW at 14:00, load factor 0.50
30 such days: 42,163 kWh
four highest half-hours: 14:00 117.0, 12:30 106.7, 12:00 105.9, 16:30 105.8
night 22:00 to 06:00: 232.6 kWh, of which base 160.0 and compressor 72.6
standing waste 11.0 kW = 88.0 kWh a night (38 % of the night energy)
= 2,640 kWh a month = 31,680 currency units
Freezer restarted at 14:30 and not at 14:00
14:00 117.0 -> 92.2 kW, 14:30 82.2 -> 87.0 kW
new peak 106.7 kW at 12:30, energy 1405.4 kWh
demand 150.0 -> 136.8 kVA, fall 13.2 kVA
demand charge 120,000 -> 109,440, difference 10,560 a month
whole bill with the surcharge: 773,760 -> 760,666, difference 13,094
Saved load_profile_and_bill.png

In the script, the working-hours loads take a random share of their full input in each half-hour, and their full input in the first half-hour after a start. That rule is a model, chosen to show the effect. A real site shows its own pattern only in its own record.

Common Mistakes



  • Blaming the starting current for the maximum demand. A start of a few seconds hardly changes a 30-minute average. Loads that run together for the whole interval set the peak.
  • Calculating load factor with kVA in one place and kW in another. Convert the maximum demand to kW first.
  • Expecting staggered starts to save energy. They lower the demand charge. The kWh stay the same.
  • Judging a month from one day. The demand charge follows the worst half-hour of the whole month, so the record must cover every day.
  • Logging at an interval longer than the demand interval, or one that is not aligned with it. The logged peak is then lower than the billed one.

Summary



  • An industrial bill has an energy line that follows the kWh of every hour, a demand line that follows the highest half-hour of the month, and often a surcharge that follows the average power factor.
  • For site E the three lines are 504,000, 120,000 and 149,760 currency units, a total of 773,760, or 18.42 per kWh against a printed price of 12.00.
  • Load factor is energy divided by maximum demand in kW and by the hours. Site E has 0.499: its peak of 117 kW is twice its average of 58.33 kW.
  • The maximum demand is an average over the demand interval, so it is set by loads that run together, not by starting current.
  • In one day of half-hourly readings, the base load was 20.0 kW, the night waste was 88 kWh (31,680 currency units a month), and a restart of everything at 14:00 set the peak. A stagger of 30 minutes lowers the peak from 117.0 kW to 106.7 kW and the demand charge by 10,560 a month.

How each lesson appears on the bill



Topic of the lessonLine of the bill that it moves
AC, RMS and phasorsNo line directly. Every line is calculated from RMS voltages and currents and the angle between them.
Three-phase systems, star and deltaEnergy, slightly: unbalance adds heating loss in motors.
Real, reactive and apparent powerDemand, because it is charged in kVA, and the kvarh behind the average power factor.
Power factor and its correctionDemand and surcharge. For site E, 120,000 becomes 98,560 and 149,760 becomes zero.
Harmonics and true power factorDemand and surcharge where the meter counts distortion, and a little energy through extra heating.
Induction motors and the nameplateEnergy through efficiency. Demand and surcharge through the low power factor of lightly loaded motors.
Motor starting and protectionAlmost nothing from the start itself. Demand, when machines start and then run heavily together.
Variable speed drivesEnergy, where the load allows a lower speed.
Transformers, generators and voltage dropEnergy through losses, and the fuel account, which is not on this bill.
Tariffs and the load profileAll three, by showing when each one is set.

Exercises



1. In a month a workshop uses 30,000 kWh, with a maximum demand of 95 kVA and an average power factor of 0.86. Build its bill on the example tariff of this lesson.

Answer

Energy . Demand . The sum is 436,000. The power factor is 4 steps below 0.90, so the surcharge is 8 percent, or 34,880. The total is 470,880 currency units.

2. For the workshop of Exercise 1, take a 30-day month and a power factor of 0.86 at the peak. Find the maximum demand in kW, the average demand and the load factor.

Answer

. . .

3. From the table of Application 2, find the energy used between 18:00 and 22:00 and the average demand in those four hours. Then find the load factor of the day after the stagger, when the peak is 106.7 kW and the energy is still 1405 kWh.

Answer

The eight values are 44.2, 44.2, 20.0, 44.2, 44.2, 20.0, 44.2 and 44.2, with a sum of 305.2. The energy is and the average demand is . After the stagger, . The load factor rose because the peak fell, which is the kind of rise that saves money.

4. The workshop of Exercise 1 has its peak of 95 kVA at a power factor of 0.86 lagging. A 15 kW water heater (unity power factor) runs in that half-hour and can be moved to the night. Find the new maximum demand in kVA and the fall in the demand charge. Why is the fall not 15 kVA?

Answer

At the peak, and . Without the heater, and is the same, so . The demand falls by 12.5 kVA and the charge by 10,000 currency units a month. kVA values do not subtract: the heater removes kW only, and the kvar of the motors stay.

5. Site E makes three changes: a capacitor bank holds the power factor at 0.95 (also at the peak), the night waste of 2,640 kWh a month is removed, and the restart is staggered so that the peak is 106.7 kW. Build the new bill and compare it with 773,760 currency units.

Answer

Energy . Maximum demand , so the demand charge is . The power factor is above 0.90, so the surcharge is zero. The total is 562,160 currency units, which is 211,600 less than before, or 27.3 percent.

References



  • J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th edition, Cengage Learning, 2017.
  • A. Thumann, T. Niehus and W. J. Younger, Handbook of Energy Audits, 9th edition, Fairmont Press, 2012.
  • B. L. Capehart, W. C. Turner and W. J. Kennedy, Guide to Energy Management, 8th edition, Fairmont Press, 2016.


© 2021-2026 SiliconWit®. All rights reserved.
Predict first

A cold store pays for kWh, for its maximum demand in kVA, and a surcharge for a low power factor. About what share of its bill is the charge for the kWh it used?

00:0006:0012:0018:00 117 kW at 14:00 work, about 105 kW night, 20 to 44 kW
See it: three meter readings make the bill

Total bill
Price of each kWh
Load factor
Surcharge rate

The lesson's example tariff: 12.00 per kWh, 800 per kVA of maximum demand, and a surcharge of 2 percent of the energy and demand charges for each 0.01 that the power factor is below 0.90. A 30-day month, 720 hours. The load factor uses the maximum demand in kW, kVA times the power factor. Prices differ by supplier; the method does not.

meter reading line of the bill kWh of the month (every hour counts) Energy charge kWh × price Highest half-hour of the month, in kVA Demand charge kVA × price Average power factor (kWh and kvarh) Surcharge, a % of the two lines above
What each line of the bill is calculated from
187 28.8 0 kVA t start, about 10 s (example): 186.9 kVA average of the interval: 29.7 kVA running at 28.8 kVA 0 30 min The start adds (186.9 − 28.8) × 10 / 1800 = 0.9 kVA to the average.
How a start counts in the half-hour average
0 20.0 44.2 117.0 kW 00:00 04:00 08:00 12:00 16:00 20:00 24:00 peak at 14:00, 117.0 kW Low bars: 20.0 kW is the base load, 44.2 kW is the base load with the compressor. Tall bars: the working day. 48 values, sum 2810.9, × 0.5 h = 1405 kWh in the day.
The day of the table: one bar for each half-hour

Check yourself

Three questions. Each wrong choice is a mistake people really make, so read the note after you answer.

1. Site E staggers the restart after lunch and its maximum demand falls by 13.2 kVA. Its kWh and its power factor (0.78, a 24 percent surcharge) do not change. How much does the monthly bill fall?

2. Another site uses the same 42,000 kWh in a month but has a maximum demand of 250 kVA, and its power factor is above 0.90. What does each kWh cost it on average, with the same tariff?

3. With a small capacitor bank, site E's average power factor rises from 0.78 to 0.86. What surcharge rate does the tariff now apply?

Watch it build: the bill of site E
METERBILL 42,000 kWh energy kWh × price 150 kVA peak demand kVA × price pf 0.78 surcharge % of both set by others levies, taxes 504,000 120,000 149,760 not here total773,760
  1. Every kWh of the month, day and night, goes to the energy line: 42,000 kWh.
  2. One half-hour only, the highest of the month, sets the demand line: 150 kVA.
  3. The average power factor of the month, 0.78, sets a surcharge on both lines.
  4. Fixed charges, levies and taxes come on top. The site cannot change them.
  5. With the example tariff: 504,000 + 120,000 + 24% surcharge 149,760 = 773,760 units.